Product overview
K-Series cabinet air-handling equipment includes horizontal, vertical, ceiling-mounted and slim ceiling-mounted arrangements. The reviewed I-type four-row hydronic coil tables distinguish chilled-water cooling and hot-water heating, with separate return-air and fresh-air duties. Full order codes and selected fan/coil conditions must be established for each project.
Key technical specifications
K-Series: horizontal, I type / 4-row coil references
Printed HGI table reference codes are not complete order codes. Air direction, water side, H return-air / X fresh-air duty, filter and non-standard static pressure must be specified separately. II type and other coil configurations are not represented.
K-Series: horizontal, I type / 4-row coil references. Printed HGI table reference codes are not complete order codes. Air direction, water side, H return-air / X fresh-air duty, filter and non-standard static pressure must be specified separately. II type and other coil configurations are not represented.
Model reference
Airflow(m³/h)
Return-air cooling(kW)
Fresh-air cooling(kW)
Return-air heating(kW)
Fresh-air heating(kW)
External static pressure(Pa)
Unit weight(kg)
Power supply
HGI50-W (table reference)
5000
29
64.2
43.2
71.9
150
195
380 V / 3N~ / 50 Hz
HGI60-W (table reference)
6000
35.5
70.9
52.9
79.4
160
215
380 V / 3N~ / 50 Hz
HGI70-W (table reference)
7000
43
87.3
64.1
97.8
170
245
380 V / 3N~ / 50 Hz
Return-air cooling: entering air 27 °C dry bulb / 19.5 °C wet bulb; entering water 7 °C, water temperature rise 5 °C. Fresh-air cooling: entering air 34 °C dry bulb / 28 °C wet bulb; same water conditions.
Return-air heating: entering air 21 °C; entering water 60 °C, water temperature drop 5 °C. Fresh-air heating: entering air 5 °C; same water conditions. Values are distinct duties, not simultaneous output.
Power supply follows the brochure's 380 V / 3N~ / 50 Hz note unless specially stated. Table references must be completed through project selection; do not infer a refrigerant or compressor for this hydronic air-handling unit.
Brochure reference ratings are not a current stock or delivery guarantee. Confirm the complete configuration, nameplate, destination-market requirements and current selection before procurement.
K-Series: vertical, I type / 4-row coil references
Printed HGI table reference codes are not complete order codes. Air direction, water side, H return-air / X fresh-air duty, filter and non-standard static pressure must be specified separately. II type and other coil configurations are not represented.
K-Series: vertical, I type / 4-row coil references. Printed HGI table reference codes are not complete order codes. Air direction, water side, H return-air / X fresh-air duty, filter and non-standard static pressure must be specified separately. II type and other coil configurations are not represented.
Model reference
Airflow(m³/h)
Return-air cooling(kW)
Fresh-air cooling(kW)
Return-air heating(kW)
Fresh-air heating(kW)
External static pressure(Pa)
Unit weight(kg)
Power supply
HGI30-L (table reference)
3000
17.8
38
26.5
42.6
130
165
380 V / 3N~ / 50 Hz
HGI35-L (table reference)
3500
21.5
43.6
32
48.8
135
180
380 V / 3N~ / 50 Hz
HGI40-L (table reference)
4000
25.2
50.8
37.5
56.9
140
190
380 V / 3N~ / 50 Hz
Return-air cooling: entering air 27 °C dry bulb / 19.5 °C wet bulb; entering water 7 °C, water temperature rise 5 °C. Fresh-air cooling: entering air 34 °C dry bulb / 28 °C wet bulb; same water conditions.
Return-air heating: entering air 21 °C; entering water 60 °C, water temperature drop 5 °C. Fresh-air heating: entering air 5 °C; same water conditions. Values are distinct duties, not simultaneous output.
Power supply follows the brochure's 380 V / 3N~ / 50 Hz note unless specially stated. Table references must be completed through project selection; do not infer a refrigerant or compressor for this hydronic air-handling unit.
Brochure reference ratings are not a current stock or delivery guarantee. Confirm the complete configuration, nameplate, destination-market requirements and current selection before procurement.
K-Series: ceiling-mounted, I type / 4-row coil references
Printed HGI table reference codes are not complete order codes. Air direction, water side, H return-air / X fresh-air duty, filter and non-standard static pressure must be specified separately. II type and other coil configurations are not represented.
K-Series: ceiling-mounted, I type / 4-row coil references. Printed HGI table reference codes are not complete order codes. Air direction, water side, H return-air / X fresh-air duty, filter and non-standard static pressure must be specified separately. II type and other coil configurations are not represented.
Model reference
Airflow(m³/h)
Return-air cooling(kW)
Fresh-air cooling(kW)
Return-air heating(kW)
Fresh-air heating(kW)
External static pressure(Pa)
Unit weight(kg)
Power supply
HGI40-D (table reference)
4000
23.2
51.3
34.6
57.5
140
170
380 V / 3N~ / 50 Hz
HGI45-D (table reference)
4500
27
54.8
40.2
61.4
145
190
380 V / 3N~ / 50 Hz
HGI50-D (table reference)
5000
31
62.6
46.2
71.8
150
205
380 V / 3N~ / 50 Hz
Return-air cooling: entering air 27 °C dry bulb / 19.5 °C wet bulb; entering water 7 °C, water temperature rise 5 °C. Fresh-air cooling: entering air 34 °C dry bulb / 28 °C wet bulb; same water conditions.
Return-air heating: entering air 21 °C; entering water 60 °C, water temperature drop 5 °C. Fresh-air heating: entering air 5 °C; same water conditions. Values are distinct duties, not simultaneous output.
Power supply follows the brochure's 380 V / 3N~ / 50 Hz note unless specially stated. Table references must be completed through project selection; do not infer a refrigerant or compressor for this hydronic air-handling unit.
Brochure reference ratings are not a current stock or delivery guarantee. Confirm the complete configuration, nameplate, destination-market requirements and current selection before procurement.
K-Series: slim ceiling-mounted, I type / 4-row coil references
Printed HGI table reference codes are not complete order codes. Air direction, water side, H return-air / X fresh-air duty, filter and non-standard static pressure must be specified separately. II type and other coil configurations are not represented.
K-Series: slim ceiling-mounted, I type / 4-row coil references. Printed HGI table reference codes are not complete order codes. Air direction, water side, H return-air / X fresh-air duty, filter and non-standard static pressure must be specified separately. II type and other coil configurations are not represented.
Model reference
Airflow(m³/h)
Return-air cooling(kW)
Fresh-air cooling(kW)
Return-air heating(kW)
Fresh-air heating(kW)
External static pressure(Pa)
Unit weight(kg)
Power supply
HGI10-B (table reference)
1000
6.2
12.6
9.3
18.9
110
125
380 V / 3N~ / 50 Hz
HGI15-B (table reference)
1500
9.1
19.2
13.6
26.8
115
125
380 V / 3N~ / 50 Hz
HGI20-B (table reference)
2000
12
25.6
18
28.7
120
145
380 V / 3N~ / 50 Hz
Return-air cooling: entering air 27 °C dry bulb / 19.5 °C wet bulb; entering water 7 °C, water temperature rise 5 °C. Fresh-air cooling: entering air 34 °C dry bulb / 28 °C wet bulb; same water conditions.
Return-air heating: entering air 21 °C; entering water 60 °C, water temperature drop 5 °C. Fresh-air heating: entering air 5 °C; same water conditions. Values are distinct duties, not simultaneous output.
Power supply follows the brochure's 380 V / 3N~ / 50 Hz note unless specially stated. Table references must be completed through project selection; do not infer a refrigerant or compressor for this hydronic air-handling unit.
Brochure reference ratings are not a current stock or delivery guarantee. Confirm the complete configuration, nameplate, destination-market requirements and current selection before procurement.
Key configuration options
W = horizontal; L = vertical; D = ceiling-mounted; B = slim ceiling-mounted arrangement.
Prepare your BOQ or model list, quantity, project location, design conditions and power supply. For stock inquiries, confirm the exact model, condition, export suitability and delivery requirements.