Hitachi Cooling & Heating / SERIES OVERVIEW

Hitachi K Series

Cabinet Air Handling Unit (AHU)

Brand
Hitachi Cooling & Heating
Series
K
Equipment category
Air-Side Equipment
Hitachi K cabinet air handling unit (ahu) series reference image
Series reference image. Individual model configurations may differ.

Product overview

K-Series cabinet air-handling equipment includes horizontal, vertical, ceiling-mounted and slim ceiling-mounted arrangements. The reviewed I-type four-row hydronic coil tables distinguish chilled-water cooling and hot-water heating, with separate return-air and fresh-air duties. Full order codes and selected fan/coil conditions must be established for each project.

Key technical specifications

K-Series: horizontal, I type / 4-row coil references

Printed HGI table reference codes are not complete order codes. Air direction, water side, H return-air / X fresh-air duty, filter and non-standard static pressure must be specified separately. II type and other coil configurations are not represented.

K-Series: horizontal, I type / 4-row coil references. Printed HGI table reference codes are not complete order codes. Air direction, water side, H return-air / X fresh-air duty, filter and non-standard static pressure must be specified separately. II type and other coil configurations are not represented.
Model referenceAirflow(m³/h)Return-air cooling(kW)Fresh-air cooling(kW)Return-air heating(kW)Fresh-air heating(kW)External static pressure(Pa)Unit weight(kg)Power supply
HGI50-W (table reference)50002964.243.271.9150195380 V / 3N~ / 50 Hz
HGI60-W (table reference)600035.570.952.979.4160215380 V / 3N~ / 50 Hz
HGI70-W (table reference)70004387.364.197.8170245380 V / 3N~ / 50 Hz
  • Return-air cooling: entering air 27 °C dry bulb / 19.5 °C wet bulb; entering water 7 °C, water temperature rise 5 °C. Fresh-air cooling: entering air 34 °C dry bulb / 28 °C wet bulb; same water conditions.
  • Return-air heating: entering air 21 °C; entering water 60 °C, water temperature drop 5 °C. Fresh-air heating: entering air 5 °C; same water conditions. Values are distinct duties, not simultaneous output.
  • Power supply follows the brochure's 380 V / 3N~ / 50 Hz note unless specially stated. Table references must be completed through project selection; do not infer a refrigerant or compressor for this hydronic air-handling unit.
  • Brochure reference ratings are not a current stock or delivery guarantee. Confirm the complete configuration, nameplate, destination-market requirements and current selection before procurement.

K-Series: vertical, I type / 4-row coil references

Printed HGI table reference codes are not complete order codes. Air direction, water side, H return-air / X fresh-air duty, filter and non-standard static pressure must be specified separately. II type and other coil configurations are not represented.

K-Series: vertical, I type / 4-row coil references. Printed HGI table reference codes are not complete order codes. Air direction, water side, H return-air / X fresh-air duty, filter and non-standard static pressure must be specified separately. II type and other coil configurations are not represented.
Model referenceAirflow(m³/h)Return-air cooling(kW)Fresh-air cooling(kW)Return-air heating(kW)Fresh-air heating(kW)External static pressure(Pa)Unit weight(kg)Power supply
HGI30-L (table reference)300017.83826.542.6130165380 V / 3N~ / 50 Hz
HGI35-L (table reference)350021.543.63248.8135180380 V / 3N~ / 50 Hz
HGI40-L (table reference)400025.250.837.556.9140190380 V / 3N~ / 50 Hz
  • Return-air cooling: entering air 27 °C dry bulb / 19.5 °C wet bulb; entering water 7 °C, water temperature rise 5 °C. Fresh-air cooling: entering air 34 °C dry bulb / 28 °C wet bulb; same water conditions.
  • Return-air heating: entering air 21 °C; entering water 60 °C, water temperature drop 5 °C. Fresh-air heating: entering air 5 °C; same water conditions. Values are distinct duties, not simultaneous output.
  • Power supply follows the brochure's 380 V / 3N~ / 50 Hz note unless specially stated. Table references must be completed through project selection; do not infer a refrigerant or compressor for this hydronic air-handling unit.
  • Brochure reference ratings are not a current stock or delivery guarantee. Confirm the complete configuration, nameplate, destination-market requirements and current selection before procurement.

K-Series: ceiling-mounted, I type / 4-row coil references

Printed HGI table reference codes are not complete order codes. Air direction, water side, H return-air / X fresh-air duty, filter and non-standard static pressure must be specified separately. II type and other coil configurations are not represented.

K-Series: ceiling-mounted, I type / 4-row coil references. Printed HGI table reference codes are not complete order codes. Air direction, water side, H return-air / X fresh-air duty, filter and non-standard static pressure must be specified separately. II type and other coil configurations are not represented.
Model referenceAirflow(m³/h)Return-air cooling(kW)Fresh-air cooling(kW)Return-air heating(kW)Fresh-air heating(kW)External static pressure(Pa)Unit weight(kg)Power supply
HGI40-D (table reference)400023.251.334.657.5140170380 V / 3N~ / 50 Hz
HGI45-D (table reference)45002754.840.261.4145190380 V / 3N~ / 50 Hz
HGI50-D (table reference)50003162.646.271.8150205380 V / 3N~ / 50 Hz
  • Return-air cooling: entering air 27 °C dry bulb / 19.5 °C wet bulb; entering water 7 °C, water temperature rise 5 °C. Fresh-air cooling: entering air 34 °C dry bulb / 28 °C wet bulb; same water conditions.
  • Return-air heating: entering air 21 °C; entering water 60 °C, water temperature drop 5 °C. Fresh-air heating: entering air 5 °C; same water conditions. Values are distinct duties, not simultaneous output.
  • Power supply follows the brochure's 380 V / 3N~ / 50 Hz note unless specially stated. Table references must be completed through project selection; do not infer a refrigerant or compressor for this hydronic air-handling unit.
  • Brochure reference ratings are not a current stock or delivery guarantee. Confirm the complete configuration, nameplate, destination-market requirements and current selection before procurement.

K-Series: slim ceiling-mounted, I type / 4-row coil references

Printed HGI table reference codes are not complete order codes. Air direction, water side, H return-air / X fresh-air duty, filter and non-standard static pressure must be specified separately. II type and other coil configurations are not represented.

K-Series: slim ceiling-mounted, I type / 4-row coil references. Printed HGI table reference codes are not complete order codes. Air direction, water side, H return-air / X fresh-air duty, filter and non-standard static pressure must be specified separately. II type and other coil configurations are not represented.
Model referenceAirflow(m³/h)Return-air cooling(kW)Fresh-air cooling(kW)Return-air heating(kW)Fresh-air heating(kW)External static pressure(Pa)Unit weight(kg)Power supply
HGI10-B (table reference)10006.212.69.318.9110125380 V / 3N~ / 50 Hz
HGI15-B (table reference)15009.119.213.626.8115125380 V / 3N~ / 50 Hz
HGI20-B (table reference)20001225.61828.7120145380 V / 3N~ / 50 Hz
  • Return-air cooling: entering air 27 °C dry bulb / 19.5 °C wet bulb; entering water 7 °C, water temperature rise 5 °C. Fresh-air cooling: entering air 34 °C dry bulb / 28 °C wet bulb; same water conditions.
  • Return-air heating: entering air 21 °C; entering water 60 °C, water temperature drop 5 °C. Fresh-air heating: entering air 5 °C; same water conditions. Values are distinct duties, not simultaneous output.
  • Power supply follows the brochure's 380 V / 3N~ / 50 Hz note unless specially stated. Table references must be completed through project selection; do not infer a refrigerant or compressor for this hydronic air-handling unit.
  • Brochure reference ratings are not a current stock or delivery guarantee. Confirm the complete configuration, nameplate, destination-market requirements and current selection before procurement.

Key configuration options

  • W = horizontal; L = vertical; D = ceiling-mounted; B = slim ceiling-mounted arrangement.
  • Choose return-air / fresh-air duty, airflow, coil type, filtration, external static pressure and connection directions.
  • The selected reference rows are not the complete portfolio or complete order codes.

Applications

  • Hydronic air treatment and ducted ventilation
  • Project-specific cooling / heating coils and airflow requirements

Information for equipment selection

  • Complete model / configuration and equipment schedule
  • Required duty and design water / ambient conditions
  • Power supply, installation space and project location
  • Destination-market requirements and current availability confirmation

Application suitability requires a review of the project requirements and selected model.

Technical documents

No model-specific technical documents are available for download on this page. Request Technical Information

Related series

REQUEST A QUOTE / TECHNICAL INFORMATION

Prepare your equipment requirements

Product reference: Hitachi K Series

Prepare your BOQ or model list, quantity, project location, design conditions and power supply. For stock inquiries, confirm the exact model, condition, export suitability and delivery requirements.

Request a Quote

Prepare your requirements on our inquiry page. Online submission is not connected yet.