Hitachi Cooling & Heating · Series overview
Hitachi AVX Series
Air-cooled inverter screw chiller / heat pump
Hitachi Cooling & Heating / SERIES OVERVIEW
Water-cooled inverter screw chiller

WV / WVP uses inverter-driven twin-screw compressors with a water-cooled condenser. The reviewed RCUF references use R134a. WVP and WV retain separate model ratings; an RCUK refrigerant option mentioned in the nomenclature needs its own technical selection.
Inverter twin-screw, water-cooled models. WV and WVP values remain model-specific; RCUK (R513A) nomenclature does not authorize reuse of RCUF ratings.
| Model reference | Cooling capacity(kW) | Cooling capacity (source)(RT) | Cooling input power(kW) | Cooling COP(W/W) | Main power supply | Refrigerant | Compressor type | Length(mm) | Width(mm) | Height(mm) | Net weight(kg) |
|---|---|---|---|---|---|---|---|---|---|---|---|
| RCUF155WV | 549 | 156.1 | 93.65 | 5.862 | 380 V / 3 phase / 50 Hz | R134a | Twin-screw, inverter driven | 3320 | 1780 | 2258 | 3780 |
| RCUF170WV | 593 | 168.7 | 102.6 | 5.782 | 380 V / 3 phase / 50 Hz | R134a | Twin-screw, inverter driven | 3320 | 1780 | 2258 | 3760 |
| RCUF210WV | 732 | 208.2 | 125.3 | 5.844 | 380 V / 3 phase / 50 Hz | R134a | Twin-screw, inverter driven | 3320 | 1780 | 2258 | 4060 |
| RCUF225WV | 791 | 225 | 137.5 | 5.754 | 380 V / 3 phase / 50 Hz | R134a | Twin-screw, inverter driven | 3320 | 1780 | 2258 | 4015 |
| RCUF260WV | 915 | 260.2 | 157.7 | 5.803 | 380 V / 3 phase / 50 Hz | R134a | Twin-screw, inverter driven | 3320 | 1780 | 2258 | 4280 |
| RCUF280WV | 988 | 281 | 172.7 | 5.722 | 380 V / 3 phase / 50 Hz | R134a | Twin-screw, inverter driven | 3320 | 1780 | 2258 | 4230 |
| RCUF310WV | 1098 | 312.3 | 187.1 | 5.867 | 380 V / 3 phase / 50 Hz | R134a | Twin-screw, inverter driven | 4691 | 1823 | 2318 | 7000 |
| RCUF365WV | 1281 | 364.3 | 221.3 | 5.789 | 380 V / 3 phase / 50 Hz | R134a | Twin-screw, inverter driven | 4691 | 1823 | 2318 | 7300 |
| RCUF420WV | 1464 | 416.4 | 253.4 | 5.778 | 380 V / 3 phase / 50 Hz | R134a | Twin-screw, inverter driven | 4691 | 1823 | 2318 | 7600 |
| RCUF470WV | 1647 | 468.4 | 277.4 | 5.938 | 380 V / 3 phase / 50 Hz | R134a | Twin-screw, inverter driven | 4691 | 1823 | 2318 | 7850 |
| RCUF520WV | 1830 | 520.5 | 318.4 | 5.748 | 380 V / 3 phase / 50 Hz | R134a | Twin-screw, inverter driven | 4691 | 1823 | 2318 | 8100 |
| RCUF300WVP | 1055 | 300 | 185.1 | 5.703 | 380 V / 3 phase / 50 Hz | R134a | Twin-screw, inverter driven | 3377 | 1818 | 2506 | 4850 |
| RCUF365WVP | 1281 | 364.2 | 218.9 | 5.852 | 380 V / 3 phase / 50 Hz | R134a | Twin-screw, inverter driven | 4691 | 1823 | 2318 | 7580 |
| RCUF420WVP | 1464 | 416.3 | 251 | 5.833 | 380 V / 3 phase / 50 Hz | R134a | Twin-screw, inverter driven | 4691 | 1823 | 2318 | 7880 |
| RCUF470WVP | 1647 | 468.3 | 283.9 | 5.802 | 380 V / 3 phase / 50 Hz | R134a | Twin-screw, inverter driven | 4691 | 1823 | 2318 | 8130 |
| RCUF520WVP | 1830 | 520.3 | 318.2 | 5.751 | 380 V / 3 phase / 50 Hz | R134a | Twin-screw, inverter driven | 4691 | 1823 | 2318 | 8380 |
Application suitability requires a review of the project requirements and selected model.
No model-specific technical documents are available for download on this page. Request Technical Information

Hitachi Cooling & Heating · Series overview
Air-cooled inverter screw chiller / heat pump

Hitachi Cooling & Heating · Series overview
Water-cooled screw chiller

Hitachi Cooling & Heating · Series overview
Water-cooled twin-screw chiller
REQUEST A QUOTE / TECHNICAL INFORMATION
Product reference: Hitachi WV / WVP Series
Prepare your BOQ or model list, quantity, project location, design conditions and power supply. For stock inquiries, confirm the exact model, condition, export suitability and delivery requirements.
Request a QuotePrepare your requirements on our inquiry page. Online submission is not connected yet.