Hitachi Cooling & Heating / SERIES OVERVIEW

Hitachi G Series

Air-Cooled Scroll Chiller / Heat Pump

Brand
Hitachi Cooling & Heating
Series
G
Equipment category
Heat Pumps
Hitachi G air-cooled scroll chiller / heat pump series reference image
Series reference image. Individual model configurations may differ.

Product overview

G-Series modular air-cooled equipment uses R410A and hermetic scroll compressors. Standard A, all-year AN and low-temperature AL configurations have different operating envelopes. The tables show individual module ratings; combined plant duty requires a separate selection.

Key technical specifications

G: standard / all-year heat-pump modules

Standard A and all-year AN variants share the printed nominal ratings; their operating envelopes differ. These are single-module ratings, not capacities for a multi-module assembly.

G: standard / all-year heat-pump modules. Standard A and all-year AN variants share the printed nominal ratings; their operating envelopes differ. These are single-module ratings, not capacities for a multi-module assembly.
Model referenceCooling capacity(kW)Cooling input power(kW)Heating capacity(kW)Heating input power(kW)Main power supplyRefrigerantCompressor typeLength(mm)Width(mm)Height(mm)Net weight(kg)CSPF (brochure)(dimensionless)
RHUA021A-G6521.16721.3380 V / 3 phase / 50 HzR410AHermetic scroll190097019605403.55
RHUA041A-G1304113341.2380 V / 3 phase / 50 HzR410AHermetic scroll2220111021608003.6
RHUA021AN-G6521.16721.3380 V / 3 phase / 50 HzR410AHermetic scroll190097019605403.55
RHUA041AN-G1304113341.2380 V / 3 phase / 50 HzR410AHermetic scroll2220111021608003.6
  • Cooling: leaving water 7 °C, water flow 0.172 m³/(h·kW), outdoor dry bulb 35 °C. Heating: leaving water 45 °C, same flow coefficient, outdoor dry bulb / wet bulb 7/6 °C.
  • Standard cooling ambient 15–45 °C; AN all-year cooling ambient −15–45 °C. Both standard/all-year heating ambient −15–25 °C. Cooling/heating leaving-water ranges are 5–15 / 35–50 °C.
  • CSPF is the brochure seasonal index, not instantaneous COP or a guaranteed project energy-saving rate.
  • Brochure reference ratings are not a current stock or delivery guarantee. Confirm the complete configuration, nameplate, destination-market requirements and current selection before procurement.

G: low-temperature AL heat-pump modules

Separate AL configuration. Standard heating, nominal low-ambient heating and lower-temperature heating have distinct test conditions; do not compare them without those conditions.

G: low-temperature AL heat-pump modules. Separate AL configuration. Standard heating, nominal low-ambient heating and lower-temperature heating have distinct test conditions; do not compare them without those conditions.
Model referenceCooling capacity(kW)Cooling input power(kW)Standard heating (7 °C air)(kW)Standard heating input(kW)Heating (−12 °C air)(kW)Heating (−20 °C air)(kW)APF (brochure)(dimensionless)Main power supplyRefrigerantCompressor typeLength(mm)Width(mm)Height(mm)Net weight(kg)
RHUA026AL-G7423.18223.752433.28380 V / 3 phase / 50 HzR410AHermetic scroll187010301960600
RHUA051AL-G14547.515546.5102813.27380 V / 3 phase / 50 HzR410AHermetic scroll221011502250940
  • Cooling: leaving water 7 °C; outdoor dry bulb 35 °C; water flow 0.172 m³/(h·kW). Standard heating: leaving water 45 °C, outdoor dry bulb / wet bulb 7/6 °C, same flow coefficient.
  • Nominal heating: leaving water 41 °C, outdoor dry bulb −12 °C / wet bulb −13.5 °C. Low-temperature heating: leaving water 41 °C, outdoor dry bulb −20 °C. These values are not the standard 7 °C heating rating.
  • AL envelope: cooling ambient 10–48 °C and leaving water 5–20 °C; heating ambient −30–30 °C and leaving water 35–60 °C. Confirm duty at the actual design point.
  • APF is the brochure seasonal index, not interchangeable with the standard-model CSPF or a project energy-saving percentage.
  • Brochure reference ratings are not a current stock or delivery guarantee. Confirm the complete configuration, nameplate, destination-market requirements and current selection before procurement.

Key configuration options

  • Standard and AN all-year configurations share nominal ratings but have different cooling ambient ranges.
  • Low-temperature AL models have their own capacity table, water-side heat exchanger and test conditions.
  • No screw, centrifugal or inverter-compressor configuration is inferred from the G-series name.

Applications

  • Modular hydronic cooling / heating
  • Project-specific outdoor chiller / heat-pump equipment selection

Information for equipment selection

  • Complete model / configuration and equipment schedule
  • Required duty and design water / ambient conditions
  • Power supply, installation space and project location
  • Destination-market requirements and current availability confirmation

Application suitability requires a review of the project requirements and selected model.

Technical documents

No model-specific technical documents are available for download on this page. Request Technical Information

Related series

REQUEST A QUOTE / TECHNICAL INFORMATION

Prepare your equipment requirements

Product reference: Hitachi G Series

Prepare your BOQ or model list, quantity, project location, design conditions and power supply. For stock inquiries, confirm the exact model, condition, export suitability and delivery requirements.

Request a Quote

Prepare your requirements on our inquiry page. Online submission is not connected yet.