Supplied YVAH-C series illustration. The reviewed 2020 table and complete inventory codes require separate configuration matching.
Product overview
YVAH is a YORK ceiling-mounted fresh-air treatment family. The reviewed 2020 brochure describes an EC fan, a cooling / heating water coil and optional humidification. Inventory codes and later C / D variants require their own configuration review; the reference table below is not a specification sheet for every stocked unit.
Inventory model references
The following supplied inventory references are available for inquiry. They are not a live stock guarantee or confirmation that every full code matches the brochure ratings below. Confirm the nameplate, complete configuration, condition and current availability.
YVAH25 / 35 / 50 references in the reviewed brochure. These ratings are not an established mapping to the complete ED62 / ED63 inventory codes or a YVAH-D dual-source variant.
YVAH: reviewed 2020 fresh-air unit references. YVAH25 / 35 / 50 references in the reviewed brochure. These ratings are not an established mapping to the complete ED62 / ED63 inventory codes or a YVAH-D dual-source variant.
Model reference
External static pressure(Pa)
Airflow (high speed)(m³/h)
Total cooling capacity(kW)
Heating capacity(kW)
Voltage(V)
Frequency(Hz)
YVAH25
100
250
3.5
3
220
50
YVAH35
100
350
5
4.2
220
50
YVAH50
120
500
7.1
6.2
220
50
100% fresh-air cooling: entering air 35 °C dry bulb / 28 °C wet bulb; entering/leaving water 7/12 °C.
100% fresh-air heating: entering air 7 °C; entering hot water 60 °C. Supply: single-phase 220 V / 50 Hz.
An optional wet-film humidifier adds air resistance; subtract its resistance from available external static pressure. Confirm the actual coil-row / filter / valve configuration before selection.
Brochure ratings apply only to the listed model references and configuration. Confirm the complete model code, nameplate and current technical selection before procurement. They do not establish stock, export suitability or lead time.
Key configuration options
Confirm coil rows, wet-film humidifier, filters, valve, pump and left / right configuration.
Do not apply this 2020 table to a dual-source YVAH-D unit or an ED62 / ED63 code without a matching technical selection.
Applications
Building fresh-air pre-cooling and pre-heating
Hydronic ventilation systems with project-specific filtration / humidity requirements
Information for equipment selection
Complete model code and required configuration
Cooling / heating duty and design water / air conditions
Electrical supply, quantity and project location
Installation arrangement and availability requirements
Application suitability requires a review of the project requirements and selected model.
Prepare your BOQ or model list, quantity, project location, design conditions and power supply. For stock inquiries, confirm the exact model, condition, export suitability and delivery requirements.